ZIEHL TR1200IP
ZIEHL TR1200IP

TR1200IP




Achtung: VLAN ID / Priorität wird nicht ünterstützt!
Warning: VLAN ID / Priority is not supported!

On     Off
::
0x
ms
ms
.0 °C
 
 
 

Download IEC 61850 IED Capability Description (ICD) file


GOOSE – message: range of measured temperature and quality

Sensor state of
single sensor
Internal error / device error
0 = no error
temperature value Quality of the temperature value
Valid temperature 0 -199..859 °C 0
Sensor = not connected 0 980 °C 0x0042
Sensor interruption 0 999 °C 0x0042
Sensor
short-circuit
0 -999 °C 0x0042
any > 0 -199..859, -999, 980,999 °C 0x0042

Quality 0x0042 = INVALID and FAILURE