Achtung: VLAN ID / Priorität wird nicht ünterstützt!
Warning: VLAN ID / Priority is not supported!
Download IEC 61850 IED Capability Description (ICD) file
GOOSE – message: range of measured temperature and quality
Sensor state of single sensor |
Internal error / device error 0 = no error |
temperature value | Quality of the temperature value |
Valid temperature | 0 | -199..859 °C | 0 |
Sensor = not connected | 0 | 980 °C | 0x0042 |
Sensor interruption | 0 | 999 °C | 0x0042 |
Sensor short-circuit |
0 | -999 °C | 0x0042 |
any | > 0 | -199..859, -999, 980,999 °C | 0x0042 |